Courbe de fragilité

NomHAZUS (2010) - Near Full, Anchored
AbréviationHAZUS-NA
Type d'unité d'installation industrielleStorage Tank
Classification des dommagesHAZUS (2010) - Storage Tank
Paramètre de risquePeak Ground Acceleration (PGA)
Unitég
Formulaire fonctionnelLog-normal (médiane)
TypeCumulative
Données
NoÉtat des dommagesMédianeÉcart-type
1.DS20.30.6
2.DS30.70.6
3.DS41.250.65
4.DS51.60.6
Courbe cumulative
Courbe discrète
Conditions de validitéBase Type: On-ground; Base Support Type: Anchored; Construction Material: Steel; Storage Condition: Atmospheric; Fill Percent: > 80 %v
PrioritéAuto
Références
Notes

See FEMA (2010), Table 8.9 (page 8-16). It is also used for tanks in refineries (Table C.8.1, page 8-99).
Eidinger et al. (2001) indicates that the curves are applicable only for (water) tanks that are at least 80% full at the time of the earthquake (Part 2, page 78).
See Di Carluccio et al. (2006), Table 1 (page 219) for probit constants, which supercedes Salzano et al. (2003) Table 5.

AccèsPublic
Créé: Serkan GIRGIN, 03/08/2011 07:46:47 – Mis à jour: Serkan GIRGIN, 12/04/2017 03:14:52