_PROPERTY_ESTIMATOR

NomCombustion rate for pool fire (TNO method)
PropriétéCombustion Rate
TypeFonction
Fonction
if ([Tb:K] > [TA:K]) {
  return 0.0010*[Hc:J/kg]*[AP:m2]/([dHv:J/kg]+[cp:J/kg.K]*([Tb:K]-[TA:K]));
} else {
  return 0.0010*[Hc:J/kg]*[AP:m2]/[dHv:J/kg];
}
Unitékg/s
Conditions de validitéSubstance Type: Flammable; Fire/Explosion Event: Pool Fire
PrioritéAuto
DésactivéNo
RéférencesU.S. EPA, "Risk Management Program Guidance for Offsite Consequence Analysis", 1999
Notes

See U.S. EPA (1999), Equations D-23 and D-26 (section D.9, pages D-19 and D-20).
Original reference is TNO (1992).

AccèsPublic
Créé: Serkan GIRGIN, 17/08/2012 08:44:02

Évaluation des risques

Risques naturels

Installations industrielles

Scientifique

Utilisateurs