Property Estimator

NameCritical filling level for floatation (Khakzad and Van Gelder, 2017)
PropertyCritical Filling Level
TypeFunction
Function
([dFW:kg/m3] * (M_PI * [D:m] * [D:m] / 4) * [WH:m] - [wt:kg]) / ([d:kg/m3] * (M_PI * [D:m] * [D:m] / 4))
Unitm
Validity ConditionsDamage State (Flood): Floatation
PrecedenceAuto
DisabledNo
AccessPublic
Created: Serkan GIRGIN, 2017/10/20 06:01:34

Risk Assessment

Natural Hazards

Industrial Plants

Scientific

Users