Fragility Curve

NameHAZUS (2010) - Anchored Chemical Tank
AbbreviationHAZUS-WTP-ACT
Plant Unit TypeStorage Tank
Damage ClassificationHAZUS (2010) - Chemical Tank
Hazard ParameterPeak Ground Acceleration (PGA)
Unitg
Functional FormLog-normal (median)
TypeCumulative
Data
NoDamage StateMedianStandard Deviation
1.DS20.40.7
2.DS30.650.7
Cumulative Curve
Discrete Curve
Validity ConditionsVolume: < 5 m3; Base Support Type: Anchored
PrecedenceAuto
ReferencesFEMA, "HAZUS-MH MR5 Technical Manual - Earthquake Model", 2010
Notes

See HAZUS (2010), Table A.8.6 (page 8-95). Custom volume condition is added to restrict fragility curve to chemical storage tanks.

AccessPublic
Created: Vincenzo ARCIDIACONO, 2014/01/28 17:14:39 – Updated: Serkan GIRGIN, 2016/03/01 15:34:57