Property Estimator

NameDistance to 1 psi overpressure for VCE (TNT-equivalency method)
PropertyEndpoint Distance
TypeFunction
Function
17 * pow([fyE:q] * [Qf:kg] * [Hc:kJ/kg] / 4680, 1/3)
Unitm
Validity ConditionsSubstance Type: Flammable; Vapor Cloud Explosion Model: TNT Equivalency; Fire/Explosion Event: Vapor Cloud Explosion; Endpoint Overpressure: 1 psi
PrecedenceAuto
DisabledNo
ReferencesU.S. EPA, "Risk Management Program Guidance for Offsite Consequence Analysis", 1999
Notes

See U.S. EPA (1999), Equation C-1 (section C-1, page C-1).
The equation is based on TNT-equivalency method. Original reference is CCPS (1994). Heat of explosion of trinitrotoluene (TNT) is taken as 4680 kJ/kg. The factor 17 is a constant associated with 1.0 psi overpressure.

AccessPublic
Created: Serkan GIRGIN, 2012/08/17 07:47:07 – Updated: Serkan GIRGIN, 2018/09/05 07:36:17